- 1. One Open Platform – Secure Real-time i-Building Management
- 2. VPN Tunnel
Internet
( Static IP)
Firewall Firewall
Internet
( Static IP)
FCC / Offices
Alarm
Printer
Report
Printer
UPS
Operator
Workstation
Niagara Html5
browserbased
Via Internet
CAT6 cable
Modbus RTU
Legend:
Internet
JACE-8000
Network Switch
BACnet MSTP
BTU Meter
VRV
FOX network
IT Network
Network Switch
Firewall
Sample System Architecture – BMS/EMS
IT Network
Network Switch
Niagara BMS/ EMS
Server with Analytics
Future Cloud
Connection
Firewall
Internet
( Static IP)
Encrypted
Device Certificate
Niagara BMS /EMS
Server on cloud
with Analytics, FM
system
Niagara Dashboards on
the go
DDC Controller
Mechanical
Fans
Network Switch
Network Switch
JACE-8000
Power
Meter
VSD
IO-Module IO-Module
Electrica
l
Lightings Genset
IO-Module
Plumbing
Fire System
Carpark
System
PV Charger
Lift And Escalator
JACE-8000
Integration
Network Switch
MQTT
PLC system
Security
System
AVG
System
JACE-8000
Solar Panels
Integration
- 3. VPN Tunnel
Internet
( Static IP)
Firewall Firewall
Internet
( Static IP)
FCC at building 1
CAT6 cable
RS-485
Legend:
Internet
Existing PLC
Controllers
BTU Meter
Power Meter
VSD
VRV
IT Network
Existing IT Network
Existing Network
Switch
Existing Network
Switch
Firewall
(by others)
Sample System Architecture For Integrated Command Centers
Existing IT Network
Existing Network
Switch
Niagara
Dashboards
Cloud
Connection
Encrypted
Device Certificate
Existing BMS Server
Firewall
(by others)
Lan Room
Existing Network
Switch
New Niagara Server
Temperature
Sensors
(LoraWan)
Presence
and
Brightness
control
Sensors
BTU Meter
Power Meter
VRV System
KNX
Modbus Modbus
Bacnet
MSTP
Hardwire
Lighting
Dimmer
Dali
JACE8000
Existing DDC
Controllers
HVAC
System
Electrical
Switchboards
Charging
Station
(Future)
OCPP
Fire
System
Solar
System
(Future)
OPC UA,
BACnet SC
Plumbing
and Sanitary
System
Interface
Interface
Communications
protocols from New
Niagara Server or
JACE to Cloud :
HTTP, JSON,
MQTT, OBIX
Existing Network
Switch
Bacnet IP
Bacnet IP or
any other
open
protocols
Bacnet IP or any other open
protocols
HVAC
System
Electrical
Switchboards
Fire
System Plumbing
and Sanitary
System
Niagara BMS /EMS
Server on cloud with
Analytics, FM system
ICC at Building 2
- 5. Tridium controllers and IO Modules
JACE 8000
EDGE- 10
IO-R 16
IO-R 34
Controllers IO Modules
- 6. • Vykon Direct Digital Controller: DDC8446 Family
GW-112
Com 1- internal
Bus
Com 2- modbus
rtu/ Bacnet mstp
DDC-8446 IO-0800 IO-6020 IO-0008
Build in with 22 points
(8UI, 4DI, 4AO and 6DO)
Either 1 of these for self forming
- 7. • Vykon Direct Digital Controller: V8044 Family
DDC-V8044
DDC-V8044 is a16 base points (8UI, 4DO, 4AO), including 8 universal inputs (AI/DI), 4
digital outputs, 4 analog outputs, which is web page functions configurable.
Communication Protocol: BACnet IP/MSTP or Modbus TCP/RTU. Able to expands
several IO through it's expansion module (IO-V0800 or IO-V6002), or Remote IO
expansion module (IO-6020-485, IO-0800-485 or IO-0008-485). It can also be applied as
a Modbus Master, Master Bridge, Bacnet Router gateway.